Industrial users of Bridgeport Twp WWTP
Bridgeport, Michigan · 2 industrial users on record · 2 sampled for PFAS · 1 above 12 ng/L PFOS
Bridgeport Twp WWTP in Bridgeport treats 1.75 MGD and receives process wastewater from 2 industrial users on record in its pretreatment programme, led by automotive, metal and equipment manufacturing (2). 2 of them have been sampled for PFAS (2 samples, 2023); 1 had a sample with PFOS above the 12 ng/L screening level.
- Bridgeport Twp WWTP: permit, flow and compliance
- PFAS sources at all Michigan plants
- All treatment plants in Michigan
- What is a significant industrial user?
PFAS sampling of the plant's industrial users
- Users sampled
- 2
- Above 12 ng/L PFOS
- 1
- Highest PFOS sample
- 14 ng/L
- Latest sample
- Nov 2023
12 ng/L is Michigan’s surface water quality value for PFOS and the screening criterion of the initiative; 170 ng/L is the value for PFOA since July 2022. Both apply to what a treatment plant discharges to a river or lake, not to what a factory sends to the sewer. An industrial user above the level has not broken a limit: it is a source the receiving plant has to follow up with sampling, a reduction plan or pretreatment.
Industrial users on record
| # | Industrial user | Industry | Type | Highest PFOS | Latest PFOS | Samples |
|---|---|---|---|---|---|---|
| 1 | Amigo Mobility Center · Bridgeport | Automotive, metal and equipment manufacturing | — | 14 ng/LNov 2023 | 14 ng/LNov 2023 | 1 |
| 2 | Orchid Orthopedic Solutions · Bridgeport | Automotive, metal and equipment manufacturing | — | 5.5 ng/LNov 2023 | 5.5 ng/LNov 2023 | 1 |
Industrial users of Bridgeport Twp WWTP: questions
Which industries discharge to Bridgeport Twp WWTP?
2 industrial users on record discharge process wastewater to Bridgeport Twp WWTP in Bridgeport, most of them in automotive, metal and equipment manufacturing (2).
Has PFAS been found in wastewater sent to Bridgeport Twp WWTP?
2 of the plant’s industrial users have been sampled for PFAS, 2 samples in 2023. 1 had at least one sample with PFOS above the 12 ng/L screening level; the highest was 14 ng/L. The level is a surface water quality value, so a sample above it marks a source the plant has to follow up, not a violation by the company.
What is an industrial pretreatment programme?
Under the Clean Water Act a treatment plant that receives industrial wastewater has to control it at the source: it permits its significant industrial users, sets local limits, inspects and samples them, and reports to the state each year. The aim is to stop pollutants that pass through or disrupt the plant, or end up in its biosolids.
Where do I find more about the industrial users of Bridgeport Twp WWTP?
This page names all 2 on record. What it leaves out, each user’s discharge flow, federal category, PFAS sampling history, source documents and contacts, is available with a free Klarifi account.
Industrial users: PFAS sampling reports that treatment plants file with EGLE under the IPP PFAS Initiative (MiEnviro Portal), extracted by Klarifi. Values are as reported by the receiving plant; a value shared by several compounds in one sample is read as the laboratory’s reporting limit and not counted as a detection. Spotted an error? Tell us and we correct it.
Try Klarifi for free
Create your own trial account and explore how Klarifi can help you.